Specifications
T10 & T10+ Thermostat Description.
|
Feature |
Description |
|
Powering Method |
Common wire required |
|
Stages: Up to 3H/2C* Heat pump Up to 2H/2C* conventional Radiant floor with slab sensor (T10+ only) |
Equipment type:
|
|
Changeover |
Manual or Auto Changeover Selectable |
|
System Setting |
Em Heat-Heat-Off-Cool-Auto |
|
Fan Setting |
Auto-On-Circ. Multiple speed settings for 2-pipe or 4-pipe fan coil units |
*4H/2C heat pump or 3H/4C conventional with T10+ & EIM.
** T10+ with EIM can control three IAQ devices.
Electrical ratings of T10 or T10+ Without EIM.
|
Terminal |
Voltage (50/60Hz) |
Running Current |
|
W (Heat) |
20-30 VAC |
0.02-1.0 A |
|
W2 (Aux) Heat |
20-30 VAC |
0.02-1.0 A |
|
E (Emergency Heat) |
20-30 VAC |
0.02-0.5 A |
|
Y (Compressor Stage 1) |
20-30 VAC |
0.02-1.0 A |
|
Y2 (Compressor Stage 2 or stage 2 fan) |
20-30 VAC |
0.02-1.0 A |
|
G (Fan) |
20-30 VAC |
0.02-0.5 A |
|
O/B (Changeover) |
20-30 VAC |
0.02-0.5 A |
|
L/A (Typically Heat Pump Fault) |
20-30 VAC |
0.02-0.5 A |
|
U (Hum, Dehum, or Vent) |
20-30 VAC |
0.02-0.5 A |
Power Consumption: 3VA
Electrical ratings of EIM (for use with T10+ models).
|
Terminal |
Voltage (50/60Hz) |
Max. Current Rating |
|
O/B |
18-30 VAC |
1.00 A |
|
Y (Compressor Stage 1) |
18-30 VAC |
1.00 A |
|
Y2 (Compressor Stage 2 or stage 2 fan) |
18-30 VAC |
1.00 A |
|
G (Fan) |
18-30 VAC |
0.50 A |
|
W1 |
18-30 VAC |
0.60 A |
|
W2/Aux 1 (Heating) |
18-30 VAC |
0.60 A |
|
W3/Aux 2 (Heating) |
18-30 VAC |
0.60 A |
|
L (Input only) |
18-30 VAC |
0.60 A |
|
U1, U1 U2, U2 U3, U3 |
18-30 VAC |
0.50 A |
RedLINK Communication:
Frequency: 900 MHz frequency range
Re-Sync Time: RedLINK devices re-establish communication within 6 minutes after AC power resumes.
Temperature Setting Range:
Heating: 40 to 90 °F (4.5 to 32 °C).
Cooling: 50 to 99 °F (10 to 37 °C).
NOTE: Adjustable high and low range-stop settings.
Humidification Setting Range:
0% to 90% RH.
Dehumidification Setting Range:
10% to 100% RH.
Humidity Display Range:
0% to 99%.
Humidity Sensor Accuracy:
± 5% RH from 30% to 50% RH at 75 F.
Cool Indication:
Display floods blue and says "Cooling to" when Cool is on.
Heat or Em Heat Indication:
Display floods orange and says "Heating to" when Heat is on.
AUX Heat Indication:
Display shows “Aux Heat On” above the room temperature.
Interstage Differential:
Comfort (default setting):
The thermostat keeps the indoor temperature within 1 degree of the setpoint (Differential less control). Unless the system is dual fuel, or a Differential setting is used, the thermostat turns on stage 2 when the capacity on stage 1 reaches 90%.
-
See ISU 3030 for cool differential options.
-
See ISU 3050 and ISU 3090 for Backup Heat Differential options.
Clock Accuracy:
1 minute per month at 77 °F (25 °C). ± 2 minutes per month over the operating ambient temperature range. Automatically updates when connected to WiFi router and registered to account.
Mounting Means:
Thermostat mounts directly on the wall in the living space using mounting screws and anchors provided. Can mount to a horizontal 2 x 4 in. junction box using J-Box adapter (included).
Model Numbers
T10+ and Accesories
|
Product |
Part Number |
Operating Ambient Temperature |
Operating Relative Humidity |
Shipping Temperature |
Dimensions in in. (mm) |
Color |
|
T10+ thermostat |
THX321WF3003W |
T10 + 37 to 102 °F. (2.8 to 38.9 °C) |
5% to 90% Non-Condensing |
-20 to 120 °F (-28.9 to 48.9 °C) |
T10+ 4.9" H x 3.7" W x 0.93" D (125.4mm H x 94.1mm W x 23.68mm D) |
White |
|
Kit with T10+ thermostat with one C7189R3002 sensor |
THX321WFS3001W |
|||||
|
Same as THX321WFS3001W kit except updated trim ring and bold idle screen font and updated cover plate |
THX321WFS3024W |
|||||
|
Kit with T10+ Thermostat, EIM, IAS, RATS/DATS |
YTHM1004R3000 |
|||||
|
Same as YTHM1004R3000 kit except updated trim ring and bold idle screen font and updated cover plate |
YTHM1004R3024 |
|||||
|
Kit with T10+ Thermostat, EIM, IAS, RATS/DATS, OAS |
YTHM1004R3001 |
|||||
|
Wireless indoor temperature, humidity, & motion sensor. Up to 20 per T10+ thermostat. (IAS) |
C7189R3002-2 |
*0 to 120 °F (17.8 to 48.9 °C) |
5% to 90% Non-Condensing |
-20 to 120 °F (-28.9 to 48.9 °C) |
2.6" W x 2.6" H x 0.78" D (66.25 W x 66.25 H x 19.7 D) |
White |
|
Wireless outdoor temperature & humidity sensor (OAS) |
C7089R3013 |
-40 to 140 °F (-40 to 60 °C) |
0% to 90% Non-Condensing |
-40 to 140 °F (-40 to 60 °C) |
5" x 3-1/2" x 1-11/16" (127 x 89 x 43) |
Grey |
|
Equipment Interface Module (EIM) |
THM04R3000 |
-40 to 165 °F (-40 to 73.9 °C) |
5% to 95% Non-Condensing |
-20 to 165 °F (-28.9 to 73.9 °C) |
4-53/64" W x 1-19/32" D (123 W x 237 H x 41 D) |
Grey |
|
Floor/Slab sensor for radiant floor heat (T10+ only. 10K ohm) |
AC112-01 |
|
||||
|
Discharge or return sensor. (Two are included with the T10+ & EIM kits) |
C7735A1000 |
|||||
* For optimal battery life, operating temperature range of 35 to 114 °F (1.7 to 45.6 °C) is recommended.
Accesories for either T10 or T10+
|
Product |
Part Number |
Dimensions in in. (mm) |
|
Large Cover Plate & J Box Adapter Included with T10 & T10+ models other than THX321WFS2001W |
THP2400A1080 |
6.11" W x 6.11" H (155.3 X 155.3) |
|
Large molded Cover Plate & J Box Adapter Included with THX321WFS2001W model of T10 & T10+ models |
Cannot be ordered as a separate accessory |
5-1/2" W x 5-13/64" H (140 x 131) |
|
Wired indoor temperature sensor (10K ohm) |
C7189U1005 |
1-1/2" W x 2-1/4" H x 3/4" D (38 W x 57 H x 19 D) |
|
Wired outdoor temperature sensor (10K ohm) |
C7089U1006 |
2-1/4" W x 3/8" H with 60" lead wires |
|
Wire saver module or C wire adapter (add a C wire). |
Various versions of this made. Starts with THP9045A |
|
T10 Thermostats and Accessories (No longer available)
|
Product |
Part Number |
Operating Ambient Temperature |
Operating Relative Humidity |
Shipping Temperature |
Dimensions in inches (mm) |
Color |
|
T10 thermostat (Discontinued) |
THX321WF2003W |
T10 Thermostat (2.8° to 38.9° C) |
5% to 90% Non Condensing |
-20 to 120 °F 28.9 to 48.9 °C) |
T10 Thermostat (125.4 H x 94.1 W x 23.68 D) |
White |
|
Kit with T10 thermostat with one C7189R2002 sensor (Discontinued) |
THX321WFS2001W |
|||||
|
Wireless indoor temperature, humidity, & motion sensor. Up to 20 per T10 thermostat (Discontinued) |
C7189R2002-2
|
*0 to 120 °F (-17.8° to 48.9°C) |
5% to 90% Non-Condensing |
-20 to 120 °F (-28.9 to 48.9 °C) |
2.6" W x 2.6" H x .78" D (66.25 W x 66.25 H x 19.7 D) |
White |
* For optimal battery life, operating temperature range of 35 to 114 °F (1.7 to 45.6 °C) is recommended.
Dimensions
Dimensions of T10 & 10+ thermostat in inches (mm)
Dimensions of C7189R3002 & C7189R2002 sensors in inches (mm)
Dimensions of THM04R3000 EIM in inches (mm)
Dimensions of C7089R3013 wireless outdoor sensor in inches (mm)
Dimensions of J-Box adapter included with all T10 & T10+ models in inches (mm)
Dimensions of molded grey cover plate included with THX321WFS2001W in inches (mm)
Dimensions of flat white cover plate included with all T10 & 10+ models other than THX321WFS2001W in inches (mm)