Wiring Diagrams
-
Use 18- to 22- gauge thermostat wire. Shielded cable is not required.
-
Set the R Slider Tab on the UWP to the up position (1 wire) for 1 transformer systems or the down position (2 wires) for 2 transformer systems. See Setting Slider Tabs.
-
Set the U Slider Tab as shown in the diagrams.
-
When T10+ is used with THM04R3000 EIM, wire only R and C to T10+ to power the thermostat. Then follow the wiring diagrams included in EIM literature.
Wiring at T10 or T10+ without EIM
Heat only: Gas, oil, or Electric furnace
|
|
G used for independent fan control only. Most Heat Only, Gas or Oil Forced Air Systems do not use a fan (G) wire. |
Cool only
1H/1C gas or electric furnace
2H/1C gas or electric furnace
2-transformer system; 1H/1C oil furnace
2-transformer system; hot water heat with air-conditioning (or hot water coil)
Hot water heat with power open zone valve
Hot water boiler, heat only
Series 20 valve (power open and power closed)
|
|
Thermostat must be configured for radiant heat with 0 (zero) cool stages. |
2H/2C Gas Furnace
Wiring a third Cool stage without EIM
|
|
G, W, W2, etc. are wired as normal. |
1H/1C Heat Pump without Aux Heat
|
|
L only connected if heat pump has a fault terminal. |
|
|
Some heat pumps use B rather than O for reversing valve. |
|
|
IMPORTANT: DO NOT connect any wire to W for heat pump applications! This can cause heat to run continuously. |
2H/1C Heat Pump with Electric Aux Heat
|
|
COMMON REQUIRED. |
|
|
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL. |
|
|
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE. |
|
|
DIFFERENT HEAT PUMP MODELS LABEL THE AUXILIARY HEAT TERMINAL DIFFERENTLY THAN SHOWN. CONSULT HEAT PUMP WIRING GUIDE. |
|
|
LOCKOUT OF AUX HEAT ON HIGH OUTDOOR TEMPERATURE CAN BE DONE THROUGH ROUTER/INTERNET CONNECTION AND APP, WIRED OUTDOOR SENSOR OR WIRELESS OUTDOOR SENSOR. |
|
|
MOST HEAT PUMPS SHARE THE SAME SET OF HEAT STRIPS FOR AUX AND EM HEAT. IN THOSE CASES E ISN’T USED. IF SEPARATE AUX AND E WIRES ARE USED, WIRE ONE SET OF STRIPS TO E TO BE ENERGIZED IN EM HEAT AND A DIFFERENT SET OF STRIPS TO AUX TO BE ENERGIZED IN AUX HEAT. |
|
|
IMPORTANT:DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS! THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.. |
2H/2C Heat pump without Aux Heat
|
|
Common required |
|
|
L only connected if heat pump has a fault terminal. |
|
|
Some heat pumps use B rather than O for reversing valve. |
|
|
IMPORTANT: DO NOT connect any wire to W for heat pump applications! This can cause heat to run continuously. |
3H/2C Heat pump with electric Aux Heat
|
|
COMMON REQUIRED. |
|
|
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL. |
|
|
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE. |
|
|
DIFFERENT HEAT PUMP MODELS LABEL THE AUXILIARY HEAT TERMINAL DIFFERENTLY THAN SHOWN. CONSULT HEAT PUMP WIRING GUIDE. |
|
|
LOCKOUT OF AUX HEAT ON HIGH OUTDOOR TEMPERATURE CAN BE DONE THROUGH ROUTER/INTERNET CONNECTION AND APP, WIRED OUTDOOR SENSOR OR WIRELESS OUTDOOR SENSOR. |
|
|
IMPORTANT:DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS! THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.. |
|
|
MOST HEAT PUMPS SHARE THE SAME SET OF HEAT STRIPS FOR AUX AND EM HEAT. IN THOSE CASES E ISN’T USED. IF SEPARATE AUX AND E WIRES ARE USED, WIRE ONE SET OF STRIPS TO E TO BE ENERGIZED IN EM HEAT AND A DIFFERENT SET OF STRIPS TO AUX TO BE ENERGIZED IN AUX HEAT. |
Dual fuel 2H/1C Heat pump
|
|
Common required |
|
|
L only connected if heat pump has a fault terminal. |
|
|
Some heat pumps use B rather than O for reversing valve. |
|
|
THE HEAT PUMP AND FURNACE HAVE SEPARATE BOARDS. THEY ARE SHOWN TOGETHER HERE TO SIMPLIFY THIS DIAGRAM. w IS FROM THE FURNACE BOARD. |
|
|
BALANCE POINT LOCKOUT CAN BE DONE THROUGH ROUTER/ INTERNET CONNECTION AND APP, WIRED OUTDOOR SENSOR OR WIRELESS OUTDOOR SENSOR. |
|
|
IMPORTANT: DO NOT connect any wire to W for heat pump applications! This can cause heat to run continuously. |
Dual Fuel, 3H/2C Heat Pump
|
|
COMMON REQUIRED. |
|
|
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL. |
|
|
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE. |
|
|
THE HEAT PUMP AND FURNACE HAVE SEPARATE BOARDS. THEY ARE SHOWN TOGETHER HERE TO SIMPLIFY THIS DIAGRAM. w IS FROM THE FURNACE BOARD. |
|
|
OPTIONAL: C7089U1006 WIRES TO THE TWO S TERMINALS. |
|
|
IMPORTANT:DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS! THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.. |
Fan Coil Unit Wiring Diagrams without EIM
Typical wiring of 4-pipe fan coil
|
|
THE R/RC AND U SLIDER SWITCHES SHOULD BE SET TO THE UP POSITION AS SHOWN. |
|
|
S TERMINALS CAN BE USED FOR A WIRED INDOOR SENSOR OR OUTDOOR SENSOR. SEE THE REMOTE SETBACK WIRING OPTIONS IF A SENSOR/SWITCH WAS WIRED TO S TERMINALS ON PREVIOUS THERMOSTAT. |
Typical wiring of 2-pipe fan coil with reheat using wired 10K/20K Heat/cool changeover pipe sensor
|
|
THE R/RC AND U SLIDER SWITCHES SHOULD BE SET TO THE UP POSITION AS SHOWN. |
|
|
S TERMINALS CAN BE USED FOR A WIRED 10K OR 20K PIPE SENSOR FOR HEAT/COOL CHANGEOVER. |
Typical wiring of 2-pipe fan coil without reheat using wired 10K/20K Heat/Cool changeover pipe sensor
|
|
THE R/RC AND U SLIDER SWITCHES SHOULD BE SET TO THE UP POSITION AS SHOWN. |
|
|
S TERMINALS CAN BE USED FOR A WIRED 10K OR 20K PIPE SENSOR FOR HEAT/COOL CHANGEOVER. SEE THE REMOTE SETBACK WIRING OPTIONS IF A SENSOR/SWITCH WAS WIRED TO S TERMINALS ON PREVIOUS THERMOSTAT. |
Typical wiring of 2-pipe fan coil with reheat using dry contact switch for Heat/Cool changeover
|
|
THE R/RC AND U SLIDER SWITCHES SHOULD BE SET TO THE UP POSITION AS SHOWN. |
|
|
WIRE THE DRY CONTACT CHANGEOVER SWITCH TO R AT THE FAN COIL UNIT AND L AT T10+ AS SHOWN. T10+ CAN BE CONFIGURED FOR THE CHANGEOVER SWITCH TO BE NORMALLY OPEN IN COOL OR HEAT MODE. |
Typical wiring of 2-pipe fan coil without reheat using dry contact switch for Heat/Cool changeover
|
|
THE R/RC AND U SLIDER SWITCHES SHOULD BE SET TO THE UP POSITION AS SHOWN. |
|
|
WIRE THE DRY CONTACT CHANGEOVER SWITCH TO R AT THE FAN COIL UNIT AND L AT T10+ AS SHOWN. T10+ CAN BE CONFIGURED FOR THE CHANGEOVER SWITCH TO BE NORMALLY OPEN IN COOL OR HEAT MODE. |
Whole house humidifier, dehumidifier, or ventilator wiring using the U slider tab
Wired to humidifier, dehumidifier, or ventilator with built-in transformer
Wired to fresh air damper powered by furnace transformer
Wired to humidifier, ventilator, or damper powered by external transformer
Wired to low speed fan terminal on HVAC for dehumidification