5. Installer Setup (ISU)
5.1 Accesing ISU
1. Press Menu and buttons for 3 seconds to enter the installer setup menu.
2. With "ISU" displayed, press Select.
3. Press or
to change the selected ISU option.
4. Press Select to move to the next ISU, and press Back button to move the previous.
5. To finish and save the selected ISUs, press Home.
5.2 Advanced Setup Options (ISU)
Note: Depending on system settings, not all options may be available.
|
# ISU |
ISU Name |
ISU Options (factory default in bold) |
||
|
120 |
Scheduling Options |
0 = Non-Programmable 2 = 5-2 Programmable 3 = 5-1-1 Programmable 4 = 7-Day Programmable |
||
|
125 |
Temperature Indication Scale |
0 = Fahrenheit 1 = Celsius |
||
|
130 |
Outdoor Sensor (TH6320U / TH6220U only) |
0 = None 1 = Wired Outdoor Sensor |
||
|
200 |
Heating System Type |
1 = Conventional Forced Air Heat 2 = Heat Pump 3 = Radiant Heat 5 = None (Cool Only) |
||
|
205 |
Heating Equipment Type |
Conventional Forced Air Heat: 1 = Standard Efficiency Gas Forced Air 2 = High Efficiency Gas Forced Air 3 = Oil Forced Air 4 = Electric Forced Air 5 = Hot Water Fan Coil
Heat Pump: 7 = Air to Air Heat Pump 8 = Geothermal Heat Pump
Radiant Heat: 9 = Hot Water Radiant Heat 12 = Steam |
||
|
218 |
Reversing Valve O/B |
0 = O (O/B in Cool) 1 = B (O/B in Heat) |
||
|
220 |
Cool Stages/Compressor Stages 200=Conv/200=HP |
0, 1, 2 Note: Only 1 compressor stage available on TH6210U model. Only 1 compressor stage available on TH6220U model if configured for heat pump. |
||
|
221 |
Heat Stages / Backup Heat Stages |
Heat Stages: 1, 2 Backup Heat Stages: 0, 1 |
||
|
230 |
Fan Control in Heat |
1 = Equipment Controls Fan 2 = Thermostat Controls Fan |
||
|
253 |
Aux/E terminal control (Fixed to “0” setting on all models except TH6320U) |
0 = Drive both Aux & E together 1 = Aux and E independent |
||
|
255 |
Backup Heat Source (Heat Pump Only) (TH6320U / TH6220U only) |
1 = Electric Forced Air 2 = Gas/Oil Forced Air (or Fossil Forced Air) |
||
|
256 |
Emergency Heat Source (TH6320U only) |
1 = Electric Forced Air 2 = Gas/Oil Forced Air (or Fossil Forced Air) |
||
|
260 |
External Fossil Fuel Kit (TH6320U / TH6220U only) |
0 = Thermostat Controls Backup Heat 1 = External Fossil Fuel Kit Controls Backup Heat |
||
|
300 |
System Changeover |
0 = Manual 1 = Automatic |
||
|
303 |
Auto Changeover Differential |
0 °F to 5 °F 0.0 °C to 2.5 °C Note: Differential is NOT deadband. Resideo uses an advanced algorithm that fixes deadband at 0 °F. The differential setting is the minimum number of degrees from set-point needed to switch from the last mode running (heat or cool) to the opposite mode when the thermostat is in auto-changeover. This is more advanced than previous thermostats. |
||
|
340 |
Backup Heat Droop |
Note: 0 (comfort) setting only available if backup heat (ISU#255) is set to Electric. |
||
|
350 |
Upstage Timer for Backup Heat |
|
||
|
355 |
Compressor Lockout / Balance Point |
-- = Off 5 °F to 60 °F (in 5 °F increments) -15.0 °C to 15.5 °C (in 2.5 °C or 3.0 °C increments) Note: Use a wired sensor to set compressor lockout / balance point on TH6320U / TH6220 |
||
|
356 |
Outdoor Lockout Backup Heat |
-- = Off 5 °F to 65 °F (in 5 °F increments) -15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments) |
||
|
365 |
Compressor Cycle Rate (Stage 1) |
1 - 6 |
||
|
366 |
Compressor Cycle Rate (Stage 2) |
1 - 6 |
||
|
370 |
Heating Cycle Rate (Stage 1) |
1 - 12 |
||
|
371 |
Heating Cycle Rate (Stage 2) |
1 - 12 |
||
|
375 |
Heating Cycle Rate Auxiliary Heat |
1 - 12 |
||
|
378 |
Heating Cycle Rate Emergency Heat (TH6320U only) |
1 - 12 |
||
|
387 |
Compressor Protection |
0 = Off 1 - 5 minutes |
||
|
425 |
Adaptive Intelligent Recovery |
0 = No 1 = Yes Note: Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time. |
||
|
430 |
Minimum Cool Setpoint |
50 °F to 99 °F (50 °F) 10.0 °C to 37.0 °C (10.0 °C) |
||
|
431 |
Maximum Heat Setpoint |
40 °F to 90 °F (90 °F) 4.5 °C to 32.0 °C (32.0 °C) |
||
|
435 |
Keypad Lockout |
Series 0-6 (setting on original T6 models): 0 = None 1 = Partial 2 = Full
Series 7 (setting current T6 models): 0 = Disabled 1 = Enabled
Note: Due to customer feedback this feature was changed. On series 0-6 thermostats, you can lock out the thermostat from the ISU the same as you can from menu lockout. For series 7 or later, this setting allows the contractor to enable or disable the lockout feature. When disabled, there is no lockout option under menu. |
||
|
500 |
Is Indoor Temperature Sensor WIRED to your system? (TH6320U /TH6220U only) |
0 = No 1 = Yes |
||
|
515 |
Indoor Sensor type (TH6320U / TH6220U only) |
0 = 10k 1 = 20k |
||
|
520 |
Which Sensors will be used for TEMPERATURE Control? (Multiple Sensors are Averaged) TH6320U /TH6220U only) |
1 = Thermostat Only 2 = Wired Only 3 = Average |
||
|
702 |
Number of Air Filters |
0 - 2 |
||
|
711 |
Air Filter 1 Replacement Reminder |
|
||
|
712 |
Air Filter 2 Replacement Reminder |
|
||
|
1400 |
Backlighting |
0 = On Demand 1 = Continuous Note: Common wire needed for continuous. |
||
|
1401 |
Backlight brightness |
1 - 5 Note: Only displayed if continuous backlight selected. |
||
|
1410 |
Clock Format |
12 / 24 |
||
|
1415 |
Daylight Saving Time |
0 = Off 1 = On |
||
|
1420 |
Temperature Display Offset |
-3 to 3F (0) -1.5 to 1.5C (0) |
ISU#: 120
Scheduling Options
0 = Non-Programmable
2 = 5-2 Programmable
3 = 5-1-1 Programmable
4 = 7-Day Programmable
ISU#: 125
Temperature Indication Scale
0 = Fahrenheit
1 = Celsius
ISU#: 130
Outdoor Sensor (TH6320U / TH6220U only)
0 = None
1 = Wired Outdoor Sensor
ISU#: 200
Heating System Type
1 = Conventional Forced Air Heat
2 = Heat Pump
3 = Radiant Heat
5 = None (Cool Only)
ISU#: 205
Heating Equipment Type
Conventional Forced Air Heat:
1 = Standard Efficiency Gas Forced Air
2 = High Efficiency Gas Forced Air
3 = Oil Forced Air
4 = Electric Forced Air
5 = Hot Water Fan Coil
Heat Pump:
7 = Air to Air Heat Pump
8 = Geothermal Heat Pump
Radiant Heat:
9 = Hot Water Radiant Heat
12 = Steam
ISU#: 218
Reversing Valve O/B
0 = O (O/B in Cool)
1 = B (O/B in Heat)
ISU#: 220
Cool Stages / Compressor Stages 200=Conv / 200=HP
0, 1, 2
Note: Only 1 compressor stage available on TH6210U model. Only 1 compressor stage available on TH6220U model if configured for heat pump.
ISU#: 221
Heat Stages / Backup Heat Stages
Heat Stages: 1, 2
Backup Heat Stages: 0, 1
ISU#: 230
Fan Control in Heat
1 = Equipment Controls Fan
2 = Thermostat Controls Fan
ISU#: 253
Aux/E terminal control (Fixed to “0” setting on all models except TH6320U)
0 = Drive both Aux & E together
1 = Aux and E independent
ISU#: 255
Backup Heat Source (Heat Pump Only) (TH6320U / TH6220U only)
1 = Electric Forced Air
2 = Gas/Oil Forced Air (or Fossil Forced Air)
ISU#: 256
Emergency Heat Source (TH6320U only)
1 = Electric Forced Air
2 = Gas/Oil Forced Air (or Fossil Forced Air)
ISU#: 260
External Fossil Fuel Kit (TH6320U / TH6220U only)
0 = Thermostat Controls Backup Heat
1 = External Fossil Fuel Kit Controls Backup Heat
ISU#: 300
System Changeover
0 = Manual
1 = Automatic
ISU#: 303
Auto Changeover Differential
0 °F to 5 °F
0.0 °C to 2.5 °C
Note: Differential is NOT deadband. Resideo uses an advanced algorithm that fixes deadband at 0 °F. The differential setting is the minimum number of degrees from set-point needed to switch from the last mode running (heat or cool) to the opposite mode when the thermostat is in auto-changeover. This is more advanced than previous thermostats.
ISU#: 340
Backup Heat Droop
0 = Comfort
2 = 2 °F
3 = 3 °F
4 = 4 °F
5 = 5 °F
6 = 6 °F
7 = 7 °F
8 = 8 °F
9 = 9 °F
10 = 10 °F
11 = 11 °F
12 = 12 °F
13 = 13 °F
14 = 14 °F
15 = 15 °F
Note: 0 (comfort) setting only available if backup heat (ISU 255) is set to Electric.
ISU#: 350
Upstage Timer for Backup Heat
0 = Off
1 = 30 minutes
2 = 45 minutes
3 = 60 minutes
4 = 75 minutes
5 = 90 minutes
6 = 2 hours
7 = 3 hours
8 = 4 hours
9 = 5 hours
10 = 6 hours
11 = 8 hours
12 = 10 hours
13 = 12 hours
14 = 14 hours
16 = 16 hours
ISU#: 355
Compressor Lockout / Balance Point
-- = Off
5 °F to 60 °F (in 5 °F increments)
-15.0 °C to 15.5 °C (in 2.5 °C or 3.0 °C increments)
Note: Use a wired sensor to set compressor lockout / balance point on TH6320U / TH6220U.
ISU#: 356
Outdoor Lockout Backup Heat
-- = Off
5 °F to 65 °F (in 5 °F increments)
-15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments)
ISU#: 365
Compressor Cycle Rate (Stage 1)
1 - 6
ISU#: 366
Compressor Cycle Rate (Stage 2)
1 - 6
ISU#: 370
Heating Cycle Rate (Stage 1)
1 - 12
ISU#: 371
Heating Cycle Rate (Stage 2)
1 - 12
ISU#: 375
Heating Cycle Rate Auxiliary Heat
1 - 12
ISU#: 378
Heating Cycle Rate Emergency Heat (TH6320U only)
1 - 12
ISU#: 387
Compressor Protection
0 = Off
1 - 5 minutes
ISU#: 425
Adaptive Intelligent Recovery
0 = No
1 = Yes
Note: Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time.
ISU#: 430
Minimum Cool Setpoint
50 °F to 99 °F (50 °F)
10.0 °C to 37.0 °C (10.0 °C)
ISU#: 431
Maximum Heat Setpoint
40 °F to 90 °F (90 °F)
4.5 °C to 32.0 °C (32.0 °C)
ISU#: 435
Keypad Lockout
Series 0-6 (setting on original T6 models):
0 = None
1 = Partial
2 = Full Series
7 (setting current T6 models):
0 = Disabled
1 = Enabled
Note: This feature has been changed in response to customer feedback. On Series 0-6 thermostats, you can lock out the thermostat from the ISU, the same as you can from menu Lockout. For Series 7 or later, this setting allows the contractor to enable or disable the Lockout feature. When disabled, there is no Lockout option under Menu.
ISU#: 500
Is Indoor Temperature Sensor WIRED to your system? (TH6320U / TH6220U only)
0 = No
1 = Yes
ISU#: 515
Indoor Sensor type (TH6320U/TH6220U only)
0 = 10k
1 = 20k
ISU#: 520
Which Sensors will be used for TEMPERATURE Control? (Multiple Sensors are Averaged) (TH6320U / TH6220U only)
1 = Thermostat Only
2 = Wired Only
3 = Average
ISU#: 702
Number of Air Filters
0 - 2
ISU#: 711
Air Filter 1 Replacement Reminder
0 = Off
1 = 10 Run Time Days
2 = 20 Run Time Days
3 = 30 Run Time Days
4 = 45 Run Time Days
5 = 60 Run Time Days
6 = 90 Run Time Days
7 = 120 Run Time Days
8 = 150 Run Time Days
9 = 30 Calendar Days
10 = 45 Calendar Days
11 = 60 Calendar Days
12 = 75 Calendar Days
13 = 3 Calendar Months
14 = 4 Calendar Months
15 = 5 Calendar Months
16 = 6 Calendar Months
17 = 9 Calendar Months
18 = 12 Calendar Months
19 = 15 Calendar Months
ISU#: 712
Air Filter 2 Replacement Reminder
0 = Off
1 = 10 Run Time Days
2 = 20 Run Time Days
3 = 30 Run Time Days
4 = 45 Run Time Days
5 = 60 Run Time Days
6 = 90 Run Time Days
7 = 120 Run Time Days
8 = 150 Run Time Days
9 = 30 Calendar Days
10 = 45 Calendar Days
11 = 60 Calendar Days
12 = 75 Calendar Days
13 = 3 Calendar Months
14 = 4 Calendar Months
15 = 5 Calendar Months
16 = 6 Calendar Months
17 = 9 Calendar Months
18 = 12 Calendar Months
19 = 15 Calendar Months
ISU#: 1400
Backlighting
0 = On Demand
1 = Continuous
Note: Common wire needed for continuous.
ISU#: 1401
Backlighting Brightness
1 - 5
Note: Only displayed if continuous backlight selected.
ISU#: 1410
Clock Format
12 / 24
ISU#: 1415
Daylight Saving Time
0 = Off
1 = On
ISU#: 1420
Temperature Display Offset
-3 to 3F (0)
-1.5 to 1.5C (0)