Installer Setup Options - Preferences
This does not show all the ISU settings available when Preferences is selected. These categories are intended to display only the settings specific to those applications. Other settings—such as temperature limits, IAQ control (humidifier, dehumidifier, ventilator), etc.—will be shown for all system types.
|
ISU # |
Heading |
Question |
Options |
Contingent previous setting? |
Notes |
|---|---|---|---|---|---|
|
1000 |
Language |
What language would you like to use? |
|
|
ISU number not displayed during initial setup |
|
1050 |
Temperature Format |
Which temperature scale would you like to use? |
|
|
|
|
3000 |
Changeover |
Changeover |
|
Any system with at least 1 Heat stage and 1 Cool stage |
See Auto Changeover Operation for Details. |
|
3260 |
Temperature Control |
Extended fan run time in cool |
|
At least 1 cool stage |
|
|
Extended fan run time in heat |
At least 1 heat stage |
|
|||
|
4090 |
Temperature Control |
Adaptive Intelligent Recovery |
|
|
When scheduling is used, this feature turns on heat or cooling early to reach the comfort set point by the scheduled comfort time |
|
4100 |
Temperature Limits |
Temperature range stops |
Minimum cool setpoint; 50F-99F (10C-37C) |
At least 1 stage of cool |
There is a correlation between these settings. For example, if minimum cool is set to 50F, minimum heat cannot be set above 40F |
|
Maximum cool setpoint; 90F-99F (32C-37C) |
At least 1 stage of cool |
||||
|
Minimum heat setpoint; 40F-50F (4.5C-10C) |
At least 1 stage of Heat |
||||
|
Maximum heat setpoint; 40F-90F (4.5 - 32.0C) |
At least 1 stage of Heat |
||||
|
4110 |
Keypad Lockout |
Keypad Lockout |
Unlocked, Partially Locked, Fully Locked |
|
|
|
14010 |
Clock Format |
Clock Format |
|
|
|
|
14015 |
Daylight Savings Time |
Daylight Savings Time |
|
|
|
|
14020 |
Display Offsets |
Indoor Display Offsets |
Indoor Temperature: (-3 to 3) in 1F increment (-1.5 to 1.5) in 0.5C increment. |
|
The display offset is applied to the Home screen, not the Priority screen. This offset is not associated with any individual sensor. |
|
Indoor Humidity: -12% to 12% RH |
|